AS Series Operation Manual 5.1.3 Relation Between the PLC Action and the Device Type _5 *1: For state setups, see HWCONFIG in ISPSoft. The PLC STOP->RUN default is “clear the non-latched area state”. The PLC RUN->STOP default is “clear the state of device Y”. *2: The timing for clearing the SM is when SM turns from OFF to ON. After PLC completes clearing, the system turns SM from ON to OFF. 5-4 Device type Non-latched area Latched area PLC action Device Y Other devices File register Other devices Power: OFF→ON Cleared Cleared Retained Retained Restore to defaults Cleared Cleared Cleared Cleared STOP ↓ RUN*1 This clears the Cleared Cleared Retained Retained non-latched area state.
This retains the Retained Retained Retained Retained non-latched area state. RUN ↓ STOP*1 This clears the Cleared Retained Retained Retained device Y state. This retains the Retained Retained Retained Retained device Y state. SM204 is ON.This clears all Cleared Cleared Retained Retained non-latched areas.*2 SM205 is ON.This clears all Retained Retained Retained Cleared latched areas.*2