AS Series Operation Manual 1. When X0.0=ON, the instruction RST will be executed and the current value of C0 will be reset to zero and the output contact of the counter C0 will be FF. 2. When X0.1 is from OFF to ON, the value of the counter increases by one increment. 3. When the value of the counter C0 reached the setting value 5, the contact of the counter C0 will be ON (the current value of C0 = the setting value = 5). After that the trigger from X0.1 will not be accepted by C0 and the current value of C0 will stay at the value 5.
X0.1 0 1 2 3 4 5 C0 (PV) (SV) 0 Y0.0,C0 _5 5.2.11 32-bit Counters (HC) Characteristics of the 32-bit counter 5-18 0.0 Item 32-bit counter Type Up/down counter Up counter High-speed counter Number HC0–HC63 HC64–HC199 HC200–HC255 Direction Counting up/down Counting up Counting up/down Setting value -2,147,483,648 to +2,147,483,647 Specification of the setting value The setting value can be either the constant or the value occupying two data registers (32-bit). Change of the current value The counter keeps counting even after the value of the counter matches the setting value. Output contact The contact is ON when the value of the addition counter matches the setting value.
The contact is reset to OFF when the value of the subtraction counter matches the setting value. Reset When the RST instruction is executed, the current value is cleared to zero, and the contact is reset to OFF.