Delta Electronics — 7.6 Backing Up a Project

AS Series Operation Manual (6) The AS Series CPU module still performs the data backup even if you click Cancel . You can turn off the AS Series CPU module to stop the data backup; however, the backup file produced is not a complete backup file, and you must delete the backup file from the memory card. If you select Memory Card (PLC Side) , the filename of the backup file is AUTOEXEC.dup , and the backup file path is Root directory of the memory card\AS300\SysDup\AUTOEXEC.dup . If there is an old backup file in the memory card, the Warning message appears. Click Replace , Archive , or Cancel in the Warning message.

If the backed up data is protected by passwords, these passwords are also backed up. (7) After you perform the data backup, click Home or Close in the CARD Utility wizard. _7 7-12 Data backup Description CPU module  Memory card The backed up data includes the PLC ID and the PLC password set in the CPU module. ISPSoft project  Computer The backed up data includes the program ID and the project password set in the ISPSoft project.