AS Series Operation Manual 7.9 CPU Error Log The system stores CPU error messages in the memory card whenever the quantity of the error messages reached to 20. You can also use special flag SM36 and special device SR36 to read the CPU error messages and state change logs. If there is error logs recorded in the memory card, the memory card keeps storing the error logs. You can change the file path to store other error logs or change the file name to store other error logs. Operation Steps to read CPU error logs and state change logs: Make sure the memory card is in the slot before reading the CPU error logs and state change logs.
(1) Set SM36 to ON and the value in SR36 to 1234 or 3456 to read the CPU error logs and state change logs. (2) The root directory path of the memory card for the error log is AS200: Memory card root directory\SDCard \ PLC CARD \ AS200 \ Log\Error.log AS300: Memory card root directory\SDCard \ PLC CARD \ AS300 \ Log\Error.log Use ISPSoft to read the error logs. ISPSoft Tools -> Review Error Log File -> Open Log File The root directory path of the memory card for the status log is AS200: Memory card root directory\SDCard \ PLC CARD \ AS200 \ Log\STATUS.log AS300: Memory card root directory\SDCard \ PLC CARD \ AS300 \ Log\STATUS.log (3) Use ISPSoft to read the status logs.
ISPSoft Tools -> Review Error Log File -> Open Log File _7 7-18 Special Device Function Code Description SR36 a. when the value is 0, it indicates there is no recording. b. when the value is 1234, it indicates the logs are stored in the memory card. c. when the value is 3456, it indicates the error logs and state change logs are stored in the memory card.