Chapter 8 Hardware Configuration The following table shows the addresses (devices) that are automatically assigned to an input/output module through HWCONFIG in ISPSoft. Refer to the following table to see the actual allowable range for program design, while editing a PLC program. Below, local indicates the IO module is connected on the right side of the CPU and Remote indicates the IO module is connected on the right side of remote module. Note: #1: the remote module itself also takes 20 devices. _8 8-7 Module type X/Y D device range Remark device range Digital module (DIO) Input points: X1.0 ~ X63.15 Output points: Y1.0 ~ Y63.15 Local: D28000 ~ D28999 Remote:

D29000 ~ D29999#1 Each module takes 20 devices. Data device number will not be shown; it is only for PLC internal use. Maximum points in total: 1024 points. For modules with less than 16 points, they will be counted as 16 points. Analog module (AIO) N/A Local: D28000 ~ D28999 Remote: D29000 ~ D29999#1 Each module takes 20 devices. Up to 16 AIO modules are configurable. Positioning module (PIO) N/A Local: D28000 ~ D28999 PU module takes 40 devices. HC module takes 20 devices. Up to 8 PIO modules are configurable locally, but not available remotely. Network module (NIO) N/A Local: D28000 ~ D28999 Remote: D29000 ~ D29999#1 Each module takes 20 devices.

Up to 4 NIO modules are configurable locally. SCM module can be used as remote module but not on the right-side of the remote module. DNET modules can only be connected locally. SIL modules can either be used locally or remotely. Communication data area: D26000 ~ D27599 Each module takes 400 devices.