Delta Electronics — 8.2.2.1 Options - System Information Page

AS Series Operation Manual  Select X Input Point If you select Enable in the previous option, you can select one input point to control the Run or Stop state of the CPU module from the dropdown list.  Constant Scan Cycle Time  Disable : disables this function. This sets the minimum scan cycle time.  Enable : when the actual scan cycle time is less than the setting time, the CPU module waits until the setting time is met, and then starts the next scan. When the actual scan time is longer than the setting time, the CPU module starts the next scan after the actual scan time completes.  Input Constant Time If you selected Enable in the previous option, you set the scan cycle time here.

If the actual scan time is less than the setting time, the CPU module waits to begin the next scan until the setting time is met. If the actual scan time is larger than the setting time, the CPU module ignores the setting time and operates according to the actual scan time. If you set the scan time longer than the watchdog timeout set, a watchdog timeout occurs when the CPU module operates.  Setting Watchdog Time This parameter sets a timeout during which the program is scanned. The CPU module sends an error if the program execution exceeds the watchdog time.

 Show Battery Low Voltage Error This parameter sets whether to show an alarm when the lithium battery for the real-time clock has low voltage or is not installed in the AS Series PLC.  Disable : disables this function.  Enable : enables the alarm when the lithium battery has low voltage or is not installed. _8  Save Error History Info  PLC : store error logs in the PLC. The PLC can store up to twenty error logs. If there are more than twenty This specifies where to store the error log. error logs, the oldest error log is overwritten by the latest error log.  PLC & SD Card :

when there are more than twenty error logs, the oldest error log is backed up to the memory card before the oldest error log is overwritten in the PLC. 8-22