Chapter 9 Ethernet Specification and Operation *1: Numbering is used for connections via the communication port. You can use connection 1 in TCP mode or UDP mode and up to 4 connections can be made per transmission. If connection 1 is used in TCP mode, the same connection number cannot be used in UDP mode. 9.3.2 EtherNet/IP Specification 9_ 9-11 (communication port)*1 UDP connection quantity Max.
data length 200 bytes SMTP (for emailing) Emailing quantity 4 4 Item AS300 Series AS200 Series AS-FEN02 Scanner Adapter Scanner Adapter Adapter General Device type Scanner / Adapter Adapter Topology type Star topology Star, linear topologies CIP Network I/O Connection CIP connection 32 8 16 8 8 number TCP connection 16 (Clients + Servers) 8 (Clients + Servers) 8 number Requested Packet 5 ms – 1000 ms 1 ms – 1000 ms Interval (RPI) Max. Transmission 3,000 pps 10,000 pps Speed Max.
Data Length/per 500 bytes 200 bytes transmission CIP Network Explicit Message Class 3 16 8 8 8 8 (Connected Type) UCMM Total 16 (for all connection types) Total 8 (for all connection types) Total 8 (for all connection types) (Non-Connected Type, only uses TCP connections) CIP Objects Identity Object (16#01) Message Router Object (16#02) Assembly Object (16#04) Connection Manager Object (16#06) Port Object (16#F4) TCP/IP Interface Object (16#F5)