Delta Electronics — 9.6.2 Error Codes & How to fix them

AS Series Operation Manual 9.6.2.2 Application Error _9 9-50 Category Error Code Description How to fix them Size parameters. H’1201012D Consumed TAG does not exist. Check if the parameters in the Consumed tag are set correctly. H’1201012E Produced TAG does not exist. Check if the parameters in the Produced tag are set correctly. H’12010204 Unconnected request timeout No response from the adapter; check if the power and the network connection for the adapter are working properly. H’12010302 Network bandwidth NOT available for data 1. Check the I/O connection limit between the scanner and the adapter. 2. Increase the RPI value or reduce the number of connections.

H’12010315 Invalid segment in connection path Check the module number and the product setup file to see if they match. Category Error Code Description How to fix them EtherNet/ IP Error H’00010203 I/O connection timeout 1. Check the network connection status. 2. Check if the module is working properly. 3. Increase the RPI value.