Delta Electronics — 9.7.7 Data Mapping

Chapter 9 Ethernet Specification and Operation 9.7.7 Data Mapping In the Controller Organizer, you can map data, including Configuration, Input and Output parameters. When you create a device I/O Configuration, the tags are added automatically.  Click Program TAGs to display the Tags window.  Tags are listed in the Name column. Tag names begin with a product name and end with C or I1 or O1 , separated from the name by a colon (:), for example CMCEIP01:C, CMCEIP01:I1, and CMCEIP01:O1.  Tag name : C indicates the tag contains information from the Adapter EDS file, including Input and Output parameters. You can edit these parameters in Studio 5000.

 Tag name : I1 indicates that the mapping starts from TAG : I1[0], and is mapped to the first parameters of the Adapter output. The length is the output length provided by the Adapter.  Tag name: O1, indicates that the mapping starts from TAG : O1[0], and is mapped to the first parameters of the Adapter Input. The length is the input length provided by the Adapter. 9_ 9-63