Delta Electronics — 9.8.10 X Register (Class ID: 350 Hex)

AS Series Operation Manual ※ 2 Interface Capability Bits 9.8.10 X Register (Class ID: 350 Hex)  Service Code  Class  Class ID : H’350 _9  Instance  H’01 : Instance Attribute, Bit Register  H’02 : Instance Attribute, Word Register  When Instance = 1, the Instance Attributes are listed below. 9-86 Bits Item Description 0 Manual Setting Requires Reset Indicates if the device requires a reset when instance attribute #6 (Interface Control attribute) changes.

0 indicates the device does not require a reset 1 indicates the device requires a rest 1 Auto-negotiate 0 indicates the interface does not support auto-negotiation 1 indicates the interface supports auto-negotiation 2 Auto-MDIX 0 indicates the interface does not support auto MDIX operation 1 indicates the interface supports auto MDIX operation 3 Manual Speed/Duplex 0 indicates the interface does not support speed/duplex setting.

(Instance attribute #6, Interface Control attribute) 1 indicates the interface supports speed/duplex setting 4-31 Reserved Should be 0 Service Code Service Name Support Description Class Attribute Instance Attribute H’0E Get Attribute Single _ _ X V Read one attribute H’32 Read Parameter _ X V Read Parameter