Delta Electronics — 2.2.2 Electrical specifications

AS Series Operation Manual  Electrical specifications for the inputs on AS200 Series. The signals passing through the inputs are 24 VDC signals. _2 2-7 Model AS228P-A / AS228R-A / AS228T-A AS218PX-A / AS218RX-A / AS218TX-A Item Number of inputs 16 (X0.0-X0.15) 8 (X0.0-X0.7) Connector type Removable terminal blocks Input type Digital input Input form Direct current (sinking or sourcing) Input voltage/ current 24 VDC, 5 mA OFF→ON >15 VDC Action level ON→OFF X0.0–X0.7: OFF→ON Response time X0.0–X0.7: ON→OFF X0.0–X0.7: 200 kHz X0.8–X0.15: 10 kHz Maximum input frequency Input impedance 3.9 k Ω Voltage direct input Sinking: The inputs are NPN transistors whose collectors are open collectors.

Sourcing: The inputs are PNP transistors whose collectors are open collectors. Input signal Electrical input isolation 500VDC Input display When the optocoupler is driven, the input LED indicator is ON. Analog inputs N/A 2 Analog input resolution N/A 12bits N/A -10V~10V (voltage mode) or 20mA~20mA (currentmode) Analog input mode Analog linearity error N/A ±1% (full scale) N/A ≧1 MΩ (Voltage mode) 250 Ω (Current mode) Analog input impedance When there is isolation between alaog and digital electricals and there is no isolation among analog channels. Isolation between analog electrical and gronunding: 500VDC Isolation between analog and digital electrical: 500VDC Analog input isolation