AS Series Operation Manual Boot-up services After the slave completes the initialization and enters the pre-operational state, it transmits the Boot- up message. 1. Other predefined CANopen communication objects (SYNC and EMCY) SYNC Object (Synchronous object) The synchronous object is the message that the master node periodically broadcasts on the CANopen network. This object recognizes the network clock signal. Every device decides whether to use the event use synchronous communication with other network devices depending on its configuration. For example, when controlling a driving device, the devices do not act immediately after they receive the command sent by the master.
They do act when they receive the synchronous message. This makes multiple devices act synchronously. The format of the SYNC message: COB-ID 80 (hex) Emergency object The emergency object is used by a CANopen device to indicate an internal error. When an emergency error occurs in the device, the device sends the emergency message (including the emergency error code), and the device enters an error state. After the error is eliminated, the device sends another emergency message with emergency error code 0, and the device enters the normal state. The format of the emergency message: Note: The value in the error register is mapped to index 1001 (hex) in the object dictionary.
If the value is occurred in the device. 0, no error occurred. If the value is 1, a normal error occurred. If the value is H’80, an internal error 10.3.3 The Predefined Connection Set In order to decrease the configuration workload of the network, CANopen defines a default identifier. In the predefined connection set, the structure of the 11-bit identifier is as follows. Function code Node ID _10 10-18 COB-ID Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 80 (hex) +Node-ID Emergency error code Error register Factory-defined error code LSB MSB