AS Series Operation Manual 6. Codes displayed in SR825 when the AS Series PLC is the slave: _10 10-30 Code Indication How to correct 0 Working normally N/A Note: When the heartbeat alam function is not activated, if the connection is normal before a disconnection occurs, the code for the slave will still be working normally after the connection is back on. A0 AS Series PLC is being initialized. -- A1 AS Series PLC is pre-operational. Check if the CANopen bus cable is properly connected. If the master communication is not activated, no handling is needed. A3 The data are being downloaded to AS Series PLC Wait to finish downloading the configured data.
B0 Heartbeat message time-out Check if the CANopen bus cable is properly connected. B1 PDO data length returned from the slave is not consistent with the length set in the node list. Reset the PDO data length in the slave and download the new setting to the AS Series PLC. F4 BUS-OFF state is detected. Check if the CANopen bus cables are properly connected and ensure that all the node devices run at the same baud rate before you reboot. FB The sending buffer in the AS Series PLC is full. Check if the CANopen bus cable is properly connected and then reboot. FC The receiving buffer in the AS Series PLC is full. Check if the CANopen bus cable is properly connected and then reboot.