Delta Electronics — 10.6 Application Example

AS Series Operation Manual 6. Program control: D25032 is given the value 256 in ISPSoft; that is, the speed command is set as 256r/min in the following diagram. 7. Program explanation When the AS300 Series PLC runs for the first time, set the parameter P3-06 for servo drive to F.  When M0 switches from OFF to ON, the instruction writes 256 to D25032 and then writes the value to the servo parameter P1-09 through RxPDO1.  When M1 switches from OFF to ON, change P4-07 to 5. DI1 and DI3 are ON. DI1 means the SERVO is ON and DI3 calls the speed specified by parameter P1-09 for servo rotation.  When M1 switches from ON to OFF, the speed command becomes 0 and the motor stops running.

_10 10-38 Data transmission on CANopen AS300 Series PLC master register A2 device bus D24032 Low word of P0-09 of servo D24033 High word of P0-09 of servo