Delta Electronics — 11.2.1 Operating Modes

Chapter 11 CPU Module Operating Principle 11.1.2 I/O Refreshing and Communication Service  Refreshing I/O The CPU module reads external I/O data periodically or outputs data to an external I/O. Refreshing the 11 I/O includes the following.  Refreshing data in a digital I/O module  Refreshing data in an analog I/O module  Refreshing data in a network module All I/O refreshing executes in the same loop. The data in an input device refreshes before a program executes, and the data in an output device refreshes after the program executes.  Communication service Communication service is the unscheduled communication service for a network module.

It includes the communication requests sent from external equipment to a CPU module, and the communication requests sent from the CPU module to the external equipment. 11.2 CPU Module Operating Modes 11.2.1 Operating Modes There are two operating modes. They can be used to control a user program and all tasks. STOP mode: A program is not executed under this mode. Users can download a module table, initialize CPU configuration and other setting, download a program, check a program, and force a bit ON/OFF. RUN mode: A program is executed under this mode. Users can not download a module table, and initialize CPU configuration and other setting.

11-3 Unit Maximum data exchange Data exchange area Depends on the number of input/output Digital I/O module Input relay/Output relay channels in the unit. Depends on the number of input/output Analog I/O module Data register channels in the unit. Network module Depends on the unit. Data register