Delta Electronics — 12.3.6.2 ERROR LED Indicators Blinking Every 0.5 Seconds

AS Series Operation Manual 12.3.6.2 ERROR LED Indicators Blinking Every 0.5 Seconds _12 The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU module and acts as a communication module. The following error codes can only be viewed with SCMSoft; when the following errors occur, they are not shown on the LED indicators and the system does not send the error messages to the CPU module. 12-24 Error Description Solution Code 16#1606 The function card setting is incorrect. 1. Check if the function card is securely installed. 2. Install a new function card or if the problem persists, contact the local authorized distributors. 3.

Check if the setting in HWCONFIG is consistent with the function card setting. 4. Install a new AS00SCM or if the problem persists, contact the local authorized distributors. Error Description Solution Code 16#1802 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again. 16#1803 Communication timeout 1. Check whether the communication cable is properly connected. 2. Check if the station number and the communication format are correctly set. 3. Check if the connection with the function card is working correctly. 16#1804 The UD Link setting is incorrect. 1. Check the settings of the UD Link. 2. Check the warning settings in the PLC.

Error Description Solution Code 16#0107 The settings in HWCONFIG and manual settings are not consistent with function card 1. Check the settings in HWCONFIG and manual settings for function card 1. 16#0108 The settings in HWCONFIG and manual settings are not consistent for function card 2. Check the settings in HWCONFIG and manual settings for function card 2. 16#0201 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again. 16#0301 Function card 1 communication timeout 1. Check if the station number and the communication format are correctly set. 2. Check if the connection with the function card is working correctly. 16#0302 Function card 2 communication timeout 1.

Check if the station number and the communication format are correctly set. 2. Check if the connection with the function card is working correctly. 16#0400 Invalid UD Link Group ID for function card 1 1. Check the UD Link settings. 2. Check the warning settings in the PLC. 16#0401 Invalid UD Link Group ID for function card 2 1. Check the UD Link settings. 2. Check the warning settings in the PLC.