AS Series Operation Manual 2.2.5 AS200 Input/Output Terminals Analog Input Two analog signal input channels: _2 You can use the program to read the values in SR to obtain the corresponding A/D conversion value for the channel. Analog Output Two analog signal output channels: You can use the instruction MOV to move the value to the SR to obtain the corresponding voltage output value.
2-17 Item Voltage Input Current input Analog Signal -10 to +10 V -20 to 20 mA Resolution 12-bit 11-bit Input impedance ≧1 MΩ 250 Ω Conversion time 3 ms / CH Analog to digital conversion range -2000 to 2000 -1000 to 1000 Digital value output SR168 (CH1) SR169 (CH2) Item Voltage output Current output Analog Signal -10 to +10 V 0 to 20 mA Resolution 12-bit 12-bit Impedance allowance ≥1 k Ω ≤500 Ω Conversion time 2ms / CH Analog to digital conversion range -2000 to 2000 0 to 4000 Digital value output SR172 (CH1) SR173 (CH2)