Delta Electronics — B.2 Function Codes and Number of Devices Supported for Modbus Protocols

0 Device Addresses B.2 Function Codes and Number of Devices Supported for Modbus Protocols Applicable to AS300 and AS200 series PLC B-3 Number of devices Number of devices Function supported supported Name Description code (FW V1.06.00 or (FW V1.06.10 or later) later) 01 Read Coil Status X, Y, M, SM, S, T, C, HC 1~256 bits 1~1600 bits 02 Read Discrete Input Status X, Y, M, SM, S, T, C, HC 1~256 bits 1~1600 bits 03 Read Holding Registers X, Y, SR, D, T, C, HC, E 1~100 words, (1~50 for HC) 1~100 words, (1~50 for HC) 04 Read Input Registers X 1~100 words 1~100 words 05 Force Single Coil Y, M, SM, S, T, C, HC 1 bit 1 bit 06 Preset Single Register Y, SR, D, T, C, HC, E 1 word 1 word 0F Force Multiple Coils Y, M, SM, S, T, C, HC 1~256 bits 1~1600 bits 10 Preset Multiple Register Y, SR, D, T, C, HC, E 1~100 words, (1~50 for HC) 1~100 words, (1~50 for HC) 17 Read/Write Multiple Register Y, SR, D, T, C, HC, E 1~100 words, (1~50 for HC) 1~100 words, (1~50 for HC)