Chapter 2 Specifications and System Configuratio n Functional specifications 2_ *1: If the measured temperature exceeds the upper limit, it only shows the maximum value. If the measured temperature is below the lower limit, it only shows the minimum value. AS04TC-A / AS08TC-A Electrical specifications 2-48 Analog-to-digital Centigrade (°C) Fahrenheit (°F) Input impedance conversion Pt100: -180°C to +800°C Ni100: -80°C to +170°C Pt1000: -180°C to +800°C Ni1000: -80°C to +170°C JPt100: -180°C to +500°C LG-Ni1000: -50°C to +180°C Cu50: -50°C to +150°C Cu100: -50°C to +150°C Pt100: -292°F to +1,472°F Ni100: -112°F to +338°F Pt1000: -292°F to +1,472°F Ni1000: -112°F to +338°F JPt100:
-292°F to +932°F LG-Ni1000: -58°F to +356°F Cu50: -58°F to +302°F Cu100: -58°F to +302°F 0–300 Ω 0–3000 Ω Rated input range*1 Range: 1–100 Average function Disconnection detection Self-diagnosis Number of analog AS04TC-A: four ; AS08TC-A: eight inputs Applicable sensor Type J, K, R, S, T, E, N and B thermocouple; input impedance: ±100mV Supply voltage 24 VDC (20.4 VDC–28.8 VDC) (-15% to +20%) Connector type Removable terminal block 25°C/77°F: The error is ±0.5% of the input within the range. -20 to +60°C/-4 to +140°F: The error is ±1% of the input within the range.
Overall accuracy Conversion time 200 ms/channel An analog circuit is isolated from a digital circuit by a digital integrated circuit, and the analog channels are isolated from one another by optocouplers. Isolation between a digital circuit and a ground: 500 VDC Isolation between an analog circuit and a ground: 500 VDC Isolation between an analog circuit and a digital circuit: 500 VDC Isolation between two group circuits: 500 VDC Isolation between the 24 VDC and a ground: 500 VDC Isolation between the analog channels: 120VAC Isolation Weight AS04TC-A: 115g ; AS08TC-A: 125g