NAVFACENGCOM MIL-HDBK-1001/5A — NAVFACENGCOM MIL-HDBK-1001/5A Roofing and Waterproofing Guide PDF

Downloaded from https://www.everyspec.com MIL-HDBK-1001/5A perimeters and at openings. Such anchorage serves several purposes: a) To prevent stress concentration at flashings, which could either split or pull loose from their backings and become vulnerable to puncture. (Loose-laid systems receive maximum membrane tensile forces at perimeters and other terminations, according to field strain tests); b) To restrain contraction in materials subject to long-term shrinkage; c) To reduce membrane wrinkling which can obstruct drainage. 6.3 Design Requirements/Considerations 6.3.1 Single-Ply Roofs. For roofs on new facilities (Refer to Section 10 for reroofing):

a) Require minimum 1/2 inch per foot (4 percent) slope, 2 inch per foot (17 percent) maximum slope for loose-laid, ballasted systems. b) Review material properties, limitations, advantages and disadvantages, and past performance of all systems under consideration (check 10-year performance in your geographical location); c) Determine wind and fire resistance during this preliminary survey. Consult Single Ply Roofing Institute (SPRI) Wind Design Guide for Ballasted Single-Ply Roof Systems Single- Ply Roofing. Ballasted systems should not be specified in coastal areas; d) Check substrate for suitability:

for sheet membranes, suitable substrates are structural concrete (cast-in- place and precast), lightweight insulating concrete with low moisture content, plywood, and rigid insulation board; for fluid- applied membranes, suitable substrates are structural concrete (cast-in-place and precast) and sprayed-in-place polyurethane foam; e) For cast-in-place concrete decks, check concrete curing agents to ensure compatibility with synthetic membranes. Some curing agents can cause poor adhesion or even premature deterioration of the membrane; 24