Kübler · N/A (no specific model mentioned) · 8 pp.

Kübler SAFE SHAFT COPYING SYSTEMS — Kübler — Operation manual

Описание систем копирования шафтного движения лифтов, включая безопасные функции, принципы работы и варианты реализации.

Related manuals

Document text

SAFE SHAFT COPYING SYSTEMS Safe shaft copying systems Whether modernization projects or new installations - the SIL3-certified shaft copying systems from Kьbler offer completely new possibilities in the field of digitalization of elevator systems. Different systems consisting of the Ants Safe Sensor LES03 combined with the PSU03 or SGT03 evaluation units offer the right solution for every application for the safe and precise determination, transmission, and processing of position and speed information of the elevator car. Autonomous system Plug & Drive The systems can be used according to the plug & drive principle with all electronic safety gear from established suppliers.

The electromechanical safety gears are triggered directly by the PSU03 or SGT03 evaluation unit based on sensor data, without going through the elevator control system. This makes the system ideal for retrofitting during modernization projects. Both the mechanical installation of the code band and sensor using a mounting kit and the commissioning and validation are quick and easy. Safety gear management MODBOX – even easier and faster Evaluation unit pre-wired with power supply and backup batteries in IP66 plastic housing. A milestone in elevator safety thanks to comprehensive gear management from PSU03 and SGT03. All components are tailored to the safety gears used.

Real-time analysis of drive data and detection of safety-critical overspeed conditions. Direct, precise, and instantaneous activation of the electromechanical safety gears in an emergency. Controlled reset and continuous status monitoring of the safety gears. Elimination of mechanical components Numerous mechanical components such as magnetic switches, ramps, and roller limit switches can be eliminated thanks to the digitally available shaft information. This also reduces the cost of installing and maintaining the elevator system. 2 kuebler.com/shaft-copying-systems

Page 2

System description Communication PSU03 / SGT03 with elevator control Evaluation unit PSU03 / SGT03 Evaluation of sensor data and direct triggering of the electro- mechanical safety gears – independent of the control system Door zone monitoring + safety circuit Sensor data from Ants LES03 to PSU03 / SGT03 E SG Sensor Ants LES03 + code band The sensor uses the code band to record the position and speed data of the elevator car. Mounting kit Safe and easy attachment and tensioning of the code band on any type of elevator rail kuebler.com/shaft-copying-systems 3

Page 3

SAFE SHAFT COPYING SYSTEMS Digitization of elevator systems - elimination of mechanical components Conventional elevator system mechanical components Kьbler – safe shaft copying systems digital position and speed detection Mechanical overspeed governor Code band Inspection switch Emergency limit switch Delay control Evaluation unit PSU03 or SGT03 Door zone monitoring Sensor Ants LES03 Flush door position Mechanical trigger of the safety gear Tensioning device for overspeed governor Switch for slack rope monitoring (governor rope) 4 kuebler.com/shaft-copying-systems Mounting kit for fixing code band and sensor

Page 4

MODBOX - System solution for modernization projects The MODBOX is a solution for modernization projects that can be used independently of the control system. The IP66 plastic housing contains the PSU03 or SGT03 evaluation unit, buffer batteries, and a power supply unit designed for the power consumption of the safety gears used. The emergency power supply ensures that the safety gears can be opened for emergency rescue even in the event of a blackout. All components in the housing are pre-wired.

Evaluation unit PSU03 / SGT03 Intelligent safety gear management The power supply units For supplying the PSU03 / SGT03 in the event of a power failure Different variants depending on the power consumption of the safety gears used The backup batteries Emergency power supply for the electromechanical safety gears used for at least 1 hour Opening the electromechanical safety gears for emergency release (e.g., in the event of a blackout) The housing ABS housing gray / transparent cover Type of protection IP66 Dimensions H x W x D: 341 x 291 x 128 or 168 mm (depending on the power supply unit) 6 cable glands 2 connected cables 9-core for: Insert when installing on the elevator cabin:

Sensor connection, connection for electromechanical safety gears power supply 230 V AC door zone monitoring security circuit kuebler.com/shaft-copying-systems 5

Page 5