Chapter 6: Rack Installation Chapter 6 Rack Installation 6-1 Overview This chapter provides a quick setup to install the SCF424 chassis into a rack. Fol lowing these steps in the order given should enable you to have the system installed within a minimal amount of time. 6-2 Unpacking the System You should inspect the box which the chassis was shipped in and note if it was damaged in any way. If the chassis itself shows damage, you should file a damage claim with the carrier who delivered it. Decide on a suitable location for the rack unit that will hold your chassis. It should be situated in a clean, dust-free area that is well ventilated.
Avoid areas where heat, electrical noise and electromagnetic fields are generated. The system needs to be placed near a grounded power outlet. Be sure to read the Rack and Server Precautions in the next section. 6-3 Preparing for Setup The box your chassis was shipped in should include two sets of rail assemblies and the mounting screws needed for installing the system into the rack. Please read this section in its entirety before you begin the installation procedure outlined in the sections that follow . Choosing a Setup Location Leave enough clearance in front of the rack to enable you to open the front door completely (~25 inches).
Leave approximately 30 inches of clearance in the back of the rack to allow for sufficient airflow and ease in servicing. This product is for installation only in a Restricted Access Location (dedicated equipment rooms, service closets and the like). 6-1