© Siemens AG 2009 1) Guide value for 4-pole standard motors for 400 V AC, 50 Hz. Selection de- pends on the concrete startup and rated data of the protected motor. 2) The motor starter protector/circuit breaker is to be set to maximum current value. 3) Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. 4) The current measuring modules required for 3UF7 are specified. For details of the 3UF7 basic units which are also required see page 9.
Selection tables 400 V AC 32 Motor starter protector/circuit breaker + contactor + SIMOCODE pro 3UF7 CLASS 40, type of coordination 2, short-circuit breaking capacity I ≥ 100 kA q 400 V AC Standard induction motor 4-pole at 400 V AC1) Setting range Overload release Motor starter pro- tector/cir- cuit breaker2) Motor starter pro- tector/circuit breaker Contactor3) Size SIMOCODE pro (current measuring module)4) Setting range Overload release Overload relay Short-circuit breaking capacity Iq Standard out- put P Motor cur- rent (guide value) I kW A A Order No. Order No. Order No. A kA 0.09 0.3 None 3RV13 21-1AC10 3RT10 24-1AP00 S0/S0 3UF7 100-1AA00-0 0.30 ...
3.00 130 0.12 0.4 None 3RV13 21-1BC10 3RT10 24-1AP00 S0/S0 0.30 ... 3.00 130 0.18 0.6 1.40 ... 2.00 3RV10 21-1BA10 3RT10 24-1AP00 S0/S0 0.30 ... 3.00 130 0.25 0.85 1.80 ... 2.50 3RV10 21-1CA10 3RT10 26-1AP00 S0/S0 0.30 ... 3.00 130 0.37 1.1 2.20 ... 3.20 3RV10 21-1DA10 3RT10 34-1AP00 S0/S2 0.30 ... 3.00 130 0.55 1.5 3.50 ... 5.00 3RV10 21-1FA10 3RT10 34-1AP00 S0/S2 0.30 ... 3.00 130 0.75 1.9 4.50 ... 6.30 3RV10 21-1GA10 3RT10 34-1AP00 S0/S2 0.30 ... 3.00 130 1.1 2.7 5.50 ... 8.00 3RV10 21-1HA10 3RT10 34-1AP00 S0/S2 3UF7 101-1AA00-0 2.40 ... 25.0 130 1.5 3.5 9.00 ... 12.5 3RV10 21-1KA10 3RT10 34-1AP00 S0/S2 2.40 ... 25.0 130 2.2 5 11.0 ... 16.0 3RV10 31-4AA10 3RT10 34-1AP00 S2/S2 2.40 ...
25.0 100 3 6.5 14.0 ... 20.0 3RV10 31-4BA10 3RT10 34-1AP00 S2/S2 2.40 ... 25.0 100 4 8.5 18.0 ... 25.0 3RV10 31-4DA10 3RT10 34-1AP00 S2/S2 2.40 ... 25.0 100 5.5 11.5 22.0 ... 32.0 3RV10 31-4EA10 3RT10 34-1AP00 S2/S2 2.40 ... 25.0 100 7.5 15.5 22.0 ... 32.0 3RV10 31-4EB10 3RT10 54-1AP36 S2/S6 3UF7 102-1AA00-0 10.0 ... 100 100 11 22 36.0 ... 50.0 3RV10 42-4HB10 3RT10 54-1AP36 S3/S6 10.0 ... 100 100 15 29 45.0 ... 63.0 3RV10 42-4JB10 3RT10 54-1AP36 S3/S6 10.0 ... 100 100 18.5 35 57.0 ... 75.0 3RV10 42-4KB10 3RT10 54-1AP36 S3/S6 3UF7 103-1AA00-0 20.0 ... 200 100 22 41 70.0 ... 90.0 3RV10 42-4LB10 3RT10 54-1AP36 S3/S6 3UF7 103-1AA00-0 20.0 ... 200 100 30 55 70.0 ...
90.0 3RV10 42-4LB10 3RT10 54-1AP36 S3/S6 3UF7 102-1AA00-0 10.0 ... 100 100 30 55 70.0 ... 90.0 3RV10 42-4LB10 3RT10 54-1AP36 S3/S6 3UF7 103-1AA00-0 20.0 ... 200 100 37 66 None 3VL27 16-3DK33 3RT10 55-1AP36 –/S6 20.0 ... 200 100 45 80 None 3VL27 16-3DK33 3RT10 56-6AP36 –/S6 20.0 ... 200 100 55 97 None 3VL37 25-3DK36 3RT10 64-6AP36 –/S10 3UF7 104-1BA00-0 63.0 ... 630 100 55 97 None 3VL37 25-3DK36 3RT12 64-6AP36 –/S10V 63.0 ... 630 100 75 132 None 3VL47 31-3DK36 3RT10 75-6AP36 –/S12 63.0 ... 630 100 90 160 None 3VL47 31-3DK36 3RT10 75-6AP36 –/S12 63.0 ... 630 100 110 195 None 3VL47 31-3DK36 3RT10 75-6AP36 –/S12 63.0 ... 630 100 132 230 None 3VL57 50-3DK36 3RT10 76-6AP36 –/S12 63.0 ...
630 100 160 280 None 3VL57 50-3DK36 3RT12 76-6AP36 –/S12V 63.0 ... 630 100