© Siemens AG 2009 Motor starter protector/circuit breaker + 3RW44 soft starter CLASS 10, type of coordination 1, short-circuit breaking capacity I q = 16... 65 kA Q1 Q11 NSB0_01016b M 3~ 400 V AC 1) At 40 °C ambient temperature (for high ambient temperatures see Catalog LV 1 T) Selection tables 400 V AC 39 Rated operational current Soft starter1) I Setting range Overload release Motor starter protector/ circuit breaker Motor starter protector/ circuit breaker Size Soft starter type Short-circuit breaking capacity Iq A A Order No. Order No. kA 29 36.0 ... 50.0 3RV10 42-4HA10 S3 3RW44 22 32 36 45.0 ... 63.0 3RV10 42-4JA10 S3 3RW44 23 32 47 57.0 ...
75.0 3RV10 42-4KA10 S3 3RW44 24 32 57 70.0 ... 90.0 3RV10 42-4LA10 S3 3RW44 25 32 77 80.0 ... 100 3RV10 42-4MA10 S3 3RW44 26 32 93 80.0 ... 100 S3 3RW44 27 32 113 None 3VL17 16-2DD36 - 3RW44 34 16 134 None - 3RW44 35 16 162 None 3VL37 25-2DC36 - 3RW44 36 65 203 None 3VL47 31-3DC36 - 3RW44 43 65 250 None - 3RW44 44 65 313 None 3VL47 40-3DC36 - 3RW44 45 65 356 None - 3RW44 46 65 432 None 3VL57 50-3DC36 - 3RW44 47 65 551 None 3VL67 80-3AB36 - 3RW44 53 65 615 None - 3RW44 54 65 693 None - 3RW44 55 65 780 None 3VL77 10-3AB36 - 3RW44 56 65 880 None - 3RW44 57 65 970 None 3VL77 12-3AB36 - 3RW44 58 65 1076 None - 3RW44 65 65 1214 None - 3RW44 66 65