© Siemens AG 2009 1) Guide value for 4-pole standard motors for 500 V AC, 50 Hz. Selection de- pends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. 3) Alternatively 3VL37 20-2SP36 also possible. 4) Alternatively 3VL37 25-2SP36 also possible. 5) Alternatively 3VL47 31-2SP36 also possible.
Selection tables 500 V AC 48 Selection tables 500 V AC Motor starter protector/circuit breaker + contactor CLASS 10, type of coordination 1, short-circuit breaking capacity I = 50 kA q 500 V AC Standard induction motor 4-pole at 500 V AC1) Setting range Overload release Motor starter pro- tector/circuit breaker Motor starter protec- tor/circuit breaker Contactor2) Size Short-circuit breaking capacity Iq Standard out- put P Motor current (guide value) I kW A A Order No. Order No. kA 0.06 0.2 0.14 ... 0.20 3RV10 11-0BA10 3RT10 15-1AP01 S00/S00 50 0.09 0.2 0.18 ... 0.25 3RV10 11-0CA10 3RT10 15-1AP01 S00/S00 50 0.12 0.3 0.22 ... 0.32 3RV10 11-0DA10 3RT10 15-1AP01 S00/S00 50 0.12 0.3 0.28 ...
0.40 3RV10 11-0EA10 3RT10 15-1AP01 S00/S00 50 0.18 0.5 0.35 ... 0.50 3RV10 11-0FA10 3RT10 15-1AP01 S00/S00 50 0.18 0.5 0.45 ... 0.63 3RV10 11-0GA10 3RT10 15-1AP01 S00/S00 50 0.25 0.7 0.55 ... 0.80 3RV10 11-0HA10 3RT10 15-1AP01 S00/S00 50 0.37 0.9 0.70 ... 1.00 3RV10 11-0JA10 3RT10 15-1AP01 S00/S00 50 0.55 1.2 0.90 ... 1.25 3RV10 11-0KA10 3RT10 15-1AP01 S00/S00 50 0.75 1.5 1.10 ... 1.60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00 50 0.75 1.5 1.40 ... 2.00 3RV10 11-1BA10 3RT10 15-1AP01 S00/S00 50 1.1 2.2 1.80 ... 2.50 3RV10 11-1CA10 3RT10 15-1AP01 S00/S00 50 1.5 2.9 2.20 ... 3.20 3RV10 11-1DA10 3RT10 15-1AP01 S00/S00 50 2.2 4.0 3.50 ... 5.00 3RV10 11-1FA10 3RT10 15-1AP01 S00/S00 50 3 5.2 4.50 ...
6.30 3RV10 11-1GA10 3RT10 15-1AP01 S00/S00 50 4 6.8 5.50 ... 8.00 3RV10 11-1HA10 3RT10 16-1AP01 S00/S00 50 5.5 9.2 7.00 ... 10.0 3RV10 11-1JA10 3RT10 17-1AP01 S00/S00 50 7.5 12.4 9.00 ... 12.5 3RV10 21-1KA10 3RT10 25-1AP00 S0/S0 50 7.5 12.4 11.0 ... 16.0 3RV10 21-4AA10 3RT10 25-1AP00 S0/S0 50 11 17.6 14.0 ... 20.0 3RV10 21-4BA10 3RT10 26-1AP00 S0/S0 50 15 23 18.0 ... 25.0 3RV10 31-4DA10 3RT10 34-1AP00 S2/S2 50 18.5 28 22.0 ... 32.0 3RV10 31-4EA10 3RT10 34-1AP00 S2/S2 50 22 33 28.0 ... 40.0 3RV10 31-4FA10 3RT10 35-1AP00 S2/S2 50 30 44 36.0 ... 45.0 3RV10 31-4GA10 3RT10 36-1AP00 S2/S2 50 30 44 40.0 ... 50.0 3RV10 31-4HA10 3RT10 36-1AP00 S2/S2 50 37 53 45.0 ...
63.0 3RV10 41-4JA10 3RT10 44-1AP00 S3/S3 50 45 64 57.0 ... 75.0 3RV10 41-4KA10 3RT10 44-1AP00 S3/S3 50 55 78 70.0 ... 90.0 3RV10 41-4LA10 3RT10 45-1AP00 S3/S3 50 75 106 64.0 ... 160 3VL27 16-2SP33 3RT10 54-6AP36 -/S6 50 90 128 64.0 ... 160 3VL27 16-2SP33 3RT10 55-6AP36 -/S6 50 110 156 64.0 ... 160 3VL27 16-2SP333) 3RT10 56-6AP36 -/S6 50 132 184 80.0 ... 200 3VL37 20-2SP364) 3RT10 64-6AP36 -/S10 50 132 184 80.0 ... 200 3VL37 20-2SP364) 3RT12 64-6AP36 -/S10V 50 160 224 100 ... 250 3VL37 25-2SP365) 3RT10 65-6AP36 -/S10 50 160 224 100 ... 250 3VL37 25-2SP365) 3RT12 65-6AP36 -/S10V 50 200 280 125 ... 315 3VL47 31-2SP36 3RT10 66-6AP36 -/S10 50 200 280 125 ...
315 3VL47 31-2SP36 3RT12 66-6AP36 -/S10V 50 250 344 200 ... 500 3VL57 50-2SP36 3RT10 75-6AP36 -/S12 50 250 344 200 ... 500 3VL57 50-2SP36 3RT12 75-6AP36 -/S12V 50 315 432 200 ... 500 3VL57 50-2SP36 3RT10 76-6AP36 -/S12 50 315 432 200 ... 500 3VL57 50-2SP36 3RT12 76-6AP36 -/S12V 50 355 488 200 ... 500 3VL57 50-2SP36 3RT10 76-6AP36 -/S12 50 355 488 200 ... 500 3VL57 50-2SP36 3RT12 76-6AP36 -/S12V 50