Siemens — Installation Guidelines for Combinations: 3RV1. 5 ... 3RV1. 8

© Siemens AG 2009 Installation Guidelines for Combinations: 3RV1. 5 ... 3RV1. 8 Distances to grounded parts for 3RT10/3RT12 contactors 3RT19 66-4EA1 terminal covers must be used on the line side of the contactor. Do not use box terminals for size S12 contac- tors. A B G H For all combinations of motor starter protectors 3RV1. 5 ... 3RV1. 8 with contactors, phase barriers must be used. NSB0_01950 Installation Guidelines 71 Motor starter protector Contactor Rated opera- tional voltage Distance to grounded or live parts A B G V mm mm mm 3RV1. 5 S00 ...S3 440/480/550/690 130 25 150 3RV1. 6/7/8 S3 ... S12 440/480/550/690 130 25 200 Motor starter protector Phase barrier 3RV1. 5 3RV19 55-5GA0 3RV1.

6/7 3RV19 75-5GA0 3RV1. 8 3RV19 85-5GA0