Smart IP43 Charger Manufacturer IP43 — 4.5. Commencing a new charge cycle

Smart IP43 Charger 4.5. Commencing a new charge cycle A new charge cycle will commence when: 1. The configured Re-bulk condition is satisfied (typically due to a large load): A. Re-bulk method set to Current and Re-bulk current is disabled (default configuration): The current output must be maintained at the maximum current output for four seconds. B. Re-bulk method is set to Current and Re-bulk current is configured with a user defined value: The current output must exceed the configured Re-bulk current for four seconds while the charger is in float or storage stage. C. Re-bulk method is set to Voltage and Re-bulk voltage offset is configured with a user defined value:

The battery voltage must drop below the configured Re-bulk voltage for one minute. D. The charger is in a VE.Smart network with synchronised charging: The battery voltage must drop below the configured Re-bulk voltage for one minute (regardless of the Re-bulk method selected). 2. The MODE button is pressed or used to select a new charge mode. 3. VictronConnect is used to select a new charge mode or change the function from Power Supply to Charger mode. 4. VictronConnect is used to disable and re-enable the charger (via the switch in the settings menu). 5. The remote terminals are used to disable and re-enable the charger (from an external switch or BMS signal). 6.

The power supply to the AC power supply has been disconnected and reconnected. Page 13 Operation