SPRUT — ANALYSIS AND DESIGN OF FLAT SLABS USING VARIOUS CODES

For short span direction, the total static design moment : 1 350 16.76 14.22 148.26 ft-kips=201.04 KNm 8 1000 M 2 0 This is distributed as follows : Negative design moment = 148.06 x 0.65 = 96.24 ft -kips = 130.50 KNm Positive design moment = 148.06 x 0.35 = 51.891 ft -kips = 70.36 KNm The column strip has a width of 2 x 14.22 2 7.11 ft 180.59 mm 4 With 2 16.76 1.17 ; 0 ( beams) 14.22 l no l 1 1 Bending moment for column strip: Negative moment for column strip = 75 % of total negative moment in the panel = 0.75 x 96.24 = 72.18 ft-kips = 97.88 KNm Positive moment for column strip = 60 % of total positive moment in the panel.

= 0.60 x 51.891 = 31.135 ft-kips = 42.21 KNm static moment along longer direction 1 350 16.76 14.22 174.75 ft-kips=237 KNm 8 1000 M 2 0 This is distributed as follows: Negative design moment = 237 x 0.65 = 154 ft-kips = 208.89 KNm Positive design moment = 237 x 0.35 = 83.00 ft -kips = 113.22 KNm The column strip has a width of 16.76 2 8.38 ft = 212.85 mm 4 14.22 0.8484 16.76 l With 2 l 1 Bending moment for column strip Negative moment for column strip = 75 % of total negative moment in the pannel = 0.75 x 154.00 = 115.50 ft-kips = 157.66 KNm Positive moment for column strip = 60 % of total positive moment in the panel. = 0.60 x 83.00 = 49.8 ft-kips = 67.977 KNm 45