Chapter 2: Server Installation Installing the Server into a Telco Rack Optional brackets (p/n MCP-290-00016-0N) are needed to install the server to a telco (open type) rack. To install the server into a Telco type rack, use the two L-shaped brackets on either side of the chassis (four total). First, determine how far follow the server will extend out the front of the rack. Larger chassis should be positioned to balance the weight between front and back. If a bezel is included on your server, remove it. Then at­ tach the two front brackets to each side of the chassis, then the two rear brackets positioned with just enough space to accommodate the width of the telco rack.

Finish by sliding the chassis into the rack and tightening the brackets to the rack. Stability hazard . The rack stabilizing mechanism must be in place, or the rack must be bolted to the floor before you slide the unit out for servicing. Failure to stabilize the rack can cause the rack to tip over. Figure 2-6. Installing the Server into a Telco Rack 2-9