Chapter 6: Advanced Chassis Setup 6-5 Checking the Airflow Checking Airflow 1. Make sure there are no objects to obstruct airflow in and out of the server. In addition, if you are using a front bezel, make sure the bezel's filter is replaced periodically. 2. Do not operate the server without drives or drive trays in the drive bays. Use only recommended server parts. 3. Make sure no wires or foreign objects obstruct airflow through the chassis. Pull all excess cabling out of the airflow path or use shorter cables. 4. The control panel LEDs inform you of system status. See “Chapter 3: System Interface” for details on the LEDs and the control panel buttons.
6-6 System Fans Four fans provide cooling for the chassis. These fans circulate air through the chassis as a means of lowering the chassis internal temperature. The SC827HQ+ system fans are hot-swappable. There is no need to power down the system when replacing fans and new tools are required for installation. Optional Fan Configurations The SC827HQ+ model chassis is designed so that the default configuration of the system is for each serverboard to control two fans (Figure 6-4). The fans are hot- swappable. Each serverboard node in the chassis is connected to the backplane through the adapter card, mounted in the serverboard drawer.
In the event that one of the serverboard drawers is removed, then the remaining serverboard will operate both fans. Fan Configurations Options SC827HQ+ Hot-Swappable Default Configuration Fan A connected to backplane, backplane connected to Node A by adapter card Fan B connected to backplane, backplane connected to Node B by adapter card Fan C connected to backplane, backplane connected to Node C by adapter card Fan D connected to backplane, backplane connected to Node D by adapter card 6-5