SuperServer 5038MD-H8TRF User's Manual System Cooling Four 8-cm fans circulate air through the chassis to lower the internal temperature. The system fans are designed to be easily changed, with no tools required and no need to remove any other parts inside the chassis. See Figure 3-2 to determine which nodes and hard drives are cooled by each fan. Replacing a System Fan 1. Determine which fan must be replaced. Use IPMI or open the chassis top cover while the system is operating and observe. Do not run the server for an extended period of time with the top cover open. 2. Remove the failed fan's power cord from the backplane. 3.
Simultaneously squeeze both release tabs on the top of the fan module. 4. Lift the fan module up and out of the chassis. 5. Place the replacement fan into the vacant space in the fan bracket while making sure the arrows on the top of the fan (indicating air direction) point in the same direction as the arrows on the other fans. 6. Put the fan back into the chassis and reconnect the cable. 7. Confirm that the fan is working properly before replacing the chassis cover. Release Tabs Figure 3-10. Replacing a Fan 40