4-2 Function Mode •C044 can be set from 0 to 100. The setting corresponds to the range of 0 to the maximum target value. 4 Alarm Output This is output when the Inverter trips. If you use the relay for alarm outputs, set and check operation,, as the SPDT contact is used for the terminals. For details, refer to the description of the relay output, "Multi-function Output Terminal ON Delay/OFF Delay" (page 4-70). Functions STOP RESET Operation RUN Stop Error STOP RESET Error Trip Alarm output External Analog Input Disconnection Detection •Outputs a signal if an error is detected in the external analog inputs (FV, FI).
4-66 Feedback value C044 Target value C044 OD ON ON Feedback value Target value ON ON Data Symbol Function name Status Description 05 AL Alarm output ON The Inverter is in trip status. OFF The Inverter is normal. Available input terminals P1-PC, MA-MC (or MB-MC) Required settings C021, C026 Data Symbol Function name Status Description 06 Dc Disconnection detection ON The Inverter is in trip status. OFF The Inverter is normal. Available input terminals P1-PC, MA-MC (or MB-MC) Required settings C021, C026, A001, A005