omron — Communication Function

4-2 Function Mode 4 Functions 4-94 Register No. Function name Parameter No. R/W Function Monitor or data range Resolution 0026h Fault monitor 3 d083 R Trip monitor 3: Factor code ⎯ 0028h R Trip monitor 3: Frequency 0.1 [Hz] 002Ah R Trip monitor 3: Current 0.1 [A] 002Bh R Trip monitor 3: Voltage 1. [V] 002Ch R Trip monitor 3: Run time (MSB) 1. [h] 002Dh R Trip monitor 3: Run time (LSB) 002Eh R Trip monitor 3: ON time (MSB) 1. [h] 002Fh R Trip monitor 3: ON time (LSB) 1014h Acceleration time 1 F002 (MSB) R/W 1 to 300000 The second decimal place is ignored when the value is over 10000 (100.0 seconds).

0.01 [s] 1015h F002 (LSB) R/W 1501h 2nd acceleration time 1 F202 (MSB) R/W 1 to 300000 The second decimal place is ignored when the value is over 10000 (100.0 seconds). 0.01 [s] 1502h F202 (LSB) R/W 1016h Deceleration time 1 F003 (MSB) R/W 1 to 300000 The second decimal place is ignored when the value is over 10000 (100.0 seconds). 0.01 [s] 1017h F003 (LSB) R/W 1503h 2nd deceleration time 1 F203 (MSB) R/W 1 to 300000 The second decimal place is ignored when the value is over 10000 (100.0 seconds). 0.01 [s] 1504h F203 (LSB) R/W 1018h Operator rotation direction selection F004 R/W 0: Forward 1: Reverse ⎯ 1019h Frequency reference selection A001 R/W 00: Digital Operator (volume) 01:

Terminal 02: Digital Operator (F001) 03: ModBus communication 10: Frequency operation result ⎯ 101Ah RUN command selection A002 R/W 01: Terminal 02: Digital Operator 03: ModBus communication 101Bh Base frequency A003 R/W 30. to maximum frequency A004 1. [Hz] 150Ch 2nd base frequency A203 R/W 30. to maximum frequency A204 1. [Hz] 101Ch Maximum frequency A004 R/W 30 to 400 1. [Hz] 150Dh 2nd maximum frequency A204 R/W 30 to 400 1. [Hz] 101Dh FV/FI selection A005 R/W 02: Switches between FV/VR via terminal AT 03: Switches between FI/VR via terminal AT 04: Terminal FV 05: Terminal FI ⎯