4-2 Function Mode 4 Functions 4-100 Register No. Function name Parameter No. R/W Function Monitor or data range Resolution 10BCh Soft lock selection b031 R/W 00: Data other than b031 cannot be changed when terminal SFT is ON. 01: Data other than b031 and the specified frequency parameter cannot be changed when terminal SFT is ON. 02: Data other than b031 cannot be changed. 03: Data other than b031 and the specified frequency parameter cannot be changed. 10: Data other than parameters changeable during operation cannot be changed. ⎯ 10C9h Selection of non-stop function at momentary power interruption b050 R/W 00: Disabled 01: Enabled (Stop) 02:

Enabled (Restart) ⎯ 10CAh Starting voltage of non-stop function at momentary power interruption b051 R/W 0 to 10000 0.1 [V] 10CBh Stop deceleration level of non-stop function at momentary power interruption b052 R/W 0 to 10000 0.1 [V] 10CCh Deceleration time of non- stop function at momentary power interruption b053 R/W 1 to 30000 0.1 [s] 10CEh Deceleration starting width of non-stop function at momentary power interruption b054 R/W 0 to 100 0.1 [Hz] 1173h Overvoltage protection proportional gain during deceleration b055 R/W 2 to 50 0.1 1174h Overvoltage protection integral time during deceleration b056 R/W 0 to 1500 0.1 [s] 10CFh AM adjustment b080 R/W 0 to 255 ⎯ 10D1h Starting frequency b082 R/W 5 to 99 0.1 [Hz] 10D2h Carrier frequency b083 R/W 20 to 120 0.1 [kHz] 10D3h Initialization selection b084 R/W 00:

Clears the trip monitor 01: Initializes data 02: Clears the trip monitor and initializes data ⎯ 10D4h Initialization parameter selection b085 R/W 00: Fixed *Do not change. ⎯ 10D5h Frequency conversion coefficient b086 R/W 1 to 999 0.1