omron — Wiring the Main Circuit Terminals

2-2 Wiring 2 Design Screw Tightening Torque „ Explanation of the Main Circuit Terminal Connection * For 3G3JX-AE ††† 's terminal symbols, R/L1 corresponds to L1, S/L2 to L2, and T/L3 to N/L3. Connect a single-phase 200-V AC input to terminals L1 and N/L3. 2-15 Model (3G3JX-) A2002 to A2007 AE002 to AE004 A2015 to A2037 A4004 to A4037 AE007 to AE022 A2055 to A2075 A4055 to A4075 Screw size W (mm) Screw size W (mm) Screw size W (mm) Main circuit M3.5 7.1 M4 9.2 M5 13 Control circuit M2 ⎯ M2 ⎯ M2 ⎯ Relay M2.5 ⎯ M2.5 ⎯ M2.5 ⎯ Ground M4 ⎯ M4 ⎯ M5 13 Screw Tightening torque M2 0.2 N•m (max. 0.25 N•m) M2.5 0.5 N•m (max. 0.6N•m) M3.5 0.8 N•m (max. 0.9 N•m) M4 1.2 N•m (max. 1.3 N•m) M5 3.0 N•m (max.

3.3 N•m) Terminal symbol Terminal name Function Connection example R/L1, S/L2, T/L3 * Main power supply input terminal Connect the input power supply. Motor ELB Power supply Do not remove the short-circuit bar between +1 and P/+2 when a DC reactor is not connected. U/T1, V/T2, W/T3 Inverter output terminal Connect to the motor. +1, P/+2 External DC reactor terminal Normally connected by the short-circuit bar. Remove the short-circuit bar between +1 and P/+2 when a DC reactor is connected. P/+2, N/- Regenerative braking unit connection terminal Connect optional regenerative braking units.