omron — Wiring the Main Circuit Terminals

2-2 Wiring Never Short-circuit or Ground the Output Terminals •Never touch the output terminals by hand. •If the output wires come into contact with metal materials, an electric shock or ground fault will occur. This is extremely hazardous. Be careful not to short-circuit the output wires. Do Not Use a Phase Advance Capacitor or Noise Filter •Doing so may result in damage to the Inverter or cause the parts to burn. Never connect a phase advance capacitor or LC/RC noise filter to the output circuit. 2 Do Not Use an Electromagnetic Switch •If a load is connected to the Inverter during running, an inrush current will actuate the overcurrent protective circuit in the Inverter.

Do not connect an electromagnetic switch or magnetic contactor (MC) to the output circuit. Design Install a Noise Filter on the Output Side Connect a noise filter to the output side of the Inverter to reduce induction and radio noise. Molded-case circuit breaker (MCCB) Power supply Inverter 3G3JX M Induction noise Signal line Radio noise AM radio Controller Induction noise: Electromagnetic induction can generate noise on the signal line, causing the controller to malfunction. Radio noise: Electromagnetic waves from the Inverter and I/O cables can cause the radio receiver to generate noise.

Countermeasures Against Induction Noise To reduce induction noise from the output side, the following method is also effective. •Run the cables collectively through the mounted metal pipe. Keeping the metal pipe at least 30 cm away from the signal line reduces induction noise. Molded-case circuit breaker (MCCB) Power supply Inverter 3G3JX M 30 cm min. Signal line Controller 2-20 Noise filter 3G3AX-NFO