omron — Maximum Frequency

4-2 Function Mode Base Frequency „ Base Frequency and Motor Voltage Match the Inverter output (frequency/voltage) to the motor rating. Be careful, especially if you set a base frequency at below 50 Hz. Otherwise, the motor may burn out. 4 * To switch to the 2nd base frequency, allocate 08 (SET) to the multi-function input terminal and then turn it on. Output voltage AVR voltage selection (A082) Functions Base frequency (A003/A203) Output frequency (Hz) •If you apply a base frequency of over 60 Hz, a special motor is required. This may require the Inverter to increase its capacity to accommodate a different applicable motor. •Select the motor voltage according to the motor specifications.

If the voltage exceeds the specified level, the motor may burn out. •The Inverter cannot output voltage beyond that of the incoming voltage. Maximum Frequency Set the maximum value of the output frequency. •The value set here will be the maximum value (e.g.,10 V in the range from 0 to 10 V) of the external analog input (frequency reference). •The maximum Inverter output voltage from base to maximum frequencies is the voltage set at AVR voltage selection A082. •The Inverter cannot output voltage beyond that of the incoming voltage. Output voltage AVR voltage selection (100%) (A082) Base frequency (A003/A203) Maximum frequency (A004/A204) 4-8 Parameter No.

Function name Data Default setting Unit A003 Base frequency 30 to max. frequency [A004] 60.0 Hz * A203 2nd base frequency 30 to max. frequency [A204] Related functions A004, A204, A081, A082