Operating response for practice System status by flag The TwinCAT severs for PLC and NC have system flags to represent and query their status (restart or number of PLC cycles etc.), which can be used for system control and to program startup behaviour. System statuses are documented in the event logger The system status and all status and error messages are documented in the Windows NT event display. Thanks to TwinCAT integration in Windows NT, access to these is easily possible using NT management tools. Cycle time and system load The execution times of the programs on a PC are set with the programming system, thus achieving a defined operating response.
The TwinCAT system displays the system load for executed programs. A load limit can be set to ensure that a defined computing capacity is available for the operator control programs and Windows NT. A system message is generated if this limit is exceeded. TwinCAT continues to operate even after user profile changes The Windows NT user can change while the TwinCAT servers are operating, thus ensuring that operators and service personnel have different access to programming systems and maintenance programs. TwinCAT integration permits user management with the Windows NT mechanisms and security standard.
TwinCAT support system analysis Thanks to large-scale integration of components and more than adequate performance of the processors, the PC architecture fundamentally offers a platform that is suitable for general automation tasks. On suitable hardware, stable real time and Windows NT operation can be guaranteed. The price for the openness of the PC world, however, is that this criterion must be checked when using hardware (example: graphics cards) or drivers. This restriction does not apply to Windows or TwinCAT, but to all operating systems. Owing to the use of unallowed methods, unsuitable hardware and software can cause problems for the operating system.
Therefore, all operating systems restrict the installation of critical (kernel mode) drivers. Beckhoff integrates a practical display of real time jitter into its product to provide an administrator with a simple means of evaluating hardware and software. During operation, a system message can draw attention to error states. System Concept 20 Version: 1.0