Accessories 12.3 SIRIUS infeed system for 3RA6 Danger, high voltage! DANGER Unless the extension modules are connected using a PE extension connector, the infeed system will NOT be grounded. If you are using the PE infeed and PE tap and decide to expand the infeed system for 3RA6 by adding extension modules, you will need to use a PE extension connector for the purpose of connecting each additional extension module to its predecessor. Note If you are installing the PE infeed on a level surface (screw fastening), it will also need to be fixed to the surface using an M4 x 16 screw.
SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 105 Step Instructions Image 1 Push the PE infeed against the right-hand/left-hand side of the screw-type infeed or extension module and then push it upwards. 1 2 3 4 5 2 Press the link wedge down. 3 Use the PE extension connector to connect the PE infeed and screw-type infeed/extension module. 4 Use the PE extension connector to connect each additional extension module to its predecessor. 5 Working from the bottom, push the PE tap into the relevant slot on the infeed or extension module until you hear it engage.