Accessories 12.3 SIRIUS infeed system for 3RA6 12.3.7 Removing the SIRIUS infeed system for 3RA6 from a DIN rail The infeed system for 3RA6 is either installed on a DIN rail or on a level surface (screw fastening). The removal process is basically the same for both mounting types. The only difference between the two is how the extension modules are fastened. As the infeed system for 3RA6 is meant to be mounted on a DIN rail as standard, the information below describes removal from a DIN rail. Requirements DANGER Danger, high voltage! Electrical voltage can result in electric shocks or burns. Before starting work, disconnect the system and devices from the power supply.
● The terminal blocks must have been disconnected. ● The compact starters and circuit breakers must have been removed. ● The PE infeed and PE tap must have been removed. Removing screw-type infeed (25/35 mm 2 ) or screw-type infeed (50/70 mmІ) from a DIN rail SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 109 Step Instructions Image 1 Pull the screw-type infeed down until it can be pulled away from the DIN rail. 1 2 2 Pull the screw-type infeed away from the DIN rail and lift it off the DIN rail's upper edge.