Accessories 12.4 3-phase busbar 12.4 3-phase busbar 12.4.1 Description of the hardware 3-phase busbars enable several compact starters to be fed using a single infeed terminal. The 3-phase busbars are finger-safe in terms of touch protection. They have been dimensioned to withstand the level of short-circuit stress that can occur on the output side of the connected compact starters. Rated operating voltage/current ● Rated operating voltage: 690 V ● Rated current: 63 A Versions Depending on the version selected, the 3-phase busbars can be used to connect between 2 and 5 compact starters.
Combining compact starters with SIRIUS circuit breakers You can combine compact starters with size S0 circuit breakers. If you wish to combine compact starters with size S00 circuit breakers you will need to use a connection piece (3RV1915-5DB). This connection piece is required, because the compact starters and size S00 circuit breakers have different depths. For additional information on combining the compact starter with SIRIUS size S00 circuit breakers, please refer to "3-phase busbar (Page 34)".
Extending 3-phase busbars The 3-phase busbar can be extended by adding another busbar (rotated by 180°) and pushing the terminal lugs of this new busbar underneath the terminals of the last compact starter (see Configuration). CAUTION Material damage to the busbar and connecting terminals! Thermal overloads can damage the busbar and connecting terminals. When extending the 3-phase busbar, please remember to observe its current carrying capacity. SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 117