Siemens — 12.5.2 Installing the 8US busbar adapter plus SIRIUS 3RA6 compact starter

Accessories 12.5 8US busbar adapter 12.5.2 Installing the 8US busbar adapter plus SIRIUS 3RA6 compact starter Requirements ● The busbars must be disconnected from the power supply when the 8US busbar adapter is mounted on the busbars. ● The compact starter must be switched off (actuator set to OFF position). Adjusting the 8US busbar adapter for the busbar system The busbar adapter can be adjusted to suit the following busbar thicknesses: ● 5 mm (delivery condition) ● 10 mm SIRIUS 3RA6 Compact Starter 122 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 Step Instructions Image 1 Push the 3 fastening blocks down.

1 5 mm 2 3 10 mm 2 Adjust the fastening blocks in accordance with the busbar thickness (5 mm/10 mm). 3 Push the fastening blocks up until they engage.