Accessories 12.6 Terminal for Type E combination motor controller, UL 508 12.6 Terminal for Type E combination motor controller, UL 508 12.6.1 Installing the terminal for a Type E self-protected combination motor controller (UL 508) According to UL 508 (Type E), line-side clearances of 1 and 2 inches are required for Type E combination motor controllers. If parallel wiring is used for the compact starter, the terminal for the self-protected combination motor controller (Type E) (3RV1928-1H) should be used. Note According to C22.2-14, terminal blocks are not required for installation in accordance with CSA requirements.
Note Supply possibilities in accordance with UL 508 (Type E) are still available when compact starters are installed with a 3-phase busbar and the infeed system for 3RA6. For additional information, please refer to "Infeed in accordance with UL 508 (Type E) (Page 36)". Procedure SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 127 Step Instructions Image 1 Attach the terminal to the compact starter's main conductor terminal from the top. 2 1 2 Screw the screw terminals tight.