Technical data 14.1 SIRIUS 3RA6 compact starter Order number 3RA61 3RA62 3RA691.-.A Service life External auxiliary switch block, internal auxiliary switch - Mechanical endurance Switching cycles 10 million - Electrical endurance AC-15, 230 V At 6 A At 3 A At 1 A At 0.3 A Switching cycles Switching cycles Switching cycles Switching cycles 200,000 500,000 2,000,000 10,000,000 DC-13, 24 V At 6 A At 3 A At 0.5 A At 0.2 A Switching cycles Switching cycles Switching cycles Switching cycles 30,000 100,000 2,000,000 10,000,000 DC-13, 110 V At 1 A At 0.55 At 0.3 A At 0.1 A At 0.04 A Switching cycles Switching cycles Switching cycles Switching cycles Switching cycles 40,000 100,000 300,000 2,000,000 10,000,000 DC-13, 220 V At 0.3 A At 0.1 A At 0.05 A At 0.018 A Switching cycles Switching cycles Switching cycles Switching cycles 110,000 650,000 2,000,000 10,000,000 Short circuit and overload signaling switches - Mechanical endurance Switching cycles 20,000 - Electrical endurance AC15 Contact reliability At 17 V, 5 mA Switching cycles 1 faulty switching operation per 100 million Switching cycles 6,050 (230 V; 3 A) Short-circuit protection External auxiliary switch block Fuse links gL/gG NEOZED 5SE, DIAZED 5SB, NH 3NA (I K ≤ 1.1 kA) A 10 Miniature circuit breakers up to 230 V with C characteristic Short-circuit current I K A 10 Internal auxiliary switch Fuse links gL/gG NEOZED 5SE, DIAZED 5SB, NH 3NA (I K ≤ 1.1 kA) A 10 Miniature circuit breakers up to 230 V with C characteristic Short-circuit current I K A 10 SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 151