Technical data 14.3 SIRIUS infeed system for 3RA6 14.3 SIRIUS infeed system for 3RA6 General data Order number 3RA68. Frequency 50/60 Hz Permissible ambient temperature Storage / transport operation °C °C -55 ... +80 -20 ... +60 1) Permissible rated current of compact starter at the following internal control cabinet temperatures: + 40 °C + 60 °C % % 100 80 Max. rated current I r max Order number Left infeed, 50/70 mmІ screw terminal with three slots, outgoing terminals with screw-type and spring-loaded connection technology, incl.
PE bar 3RA6813-8AB 3RA6813-8AC A 100 Left infeed, 25/35 mmІ screw terminal with three slots, outgoing terminals with screw-type and spring-loaded connection technology, incl.
PE bar 3RA6812-8AB 3RA6812-8AC A 63 Left or right infeed, 25/35 mmІ, with spring- loaded connection technology 3RA6830-5AC A 63 Extension connector 3RA6890-1AB A 63 Installation altitude m 2000 m above sea level without any restrictions Vibratory load f = 1 to 6 Hz; d = 15 mm 10 cycles f = 150 Hz; a = 2g Shock a = 60 m/s 2 (6g) with 10 ms every 3 All axes subjected to shock Degree of protection According to IEC / EN 60947-1 IP20 (connection compartment IP 00) Touch protection According to DIN EN 50274 Finger-safe Rated operating voltage U e V 690 AC Degree of pollution 3 Short-circuit protection for spring-loaded infeed 4 mmІ 6 mmІ 10 mmІ 16 mmІ/25 mmІ I d,max I d,max I d,max I d,max 3RV1021-4DA10 2) 3RV1031-4EA10 2) 3RV1031-4HA10 2) 3RV1041-4JA10 2) SIRIUS 3RA6 Compact Starter 156 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02