Configuration 4.1 SIRIUS 3RA6 compact starter Required control power supply Depending on the version, the compact starter requires the following control power supply (AC/DC): ● 24 V ● 42 to 70 V ● 110 to 240 V Operating temperature The compact starter has been designed for use with ambient temperatures ranging from - 20 °C to + 40 °C. Derating Within the temperature range + 40 °C to + 60 °C, derating of the compact starter's permissible rated current is necessary if: ● Several compact starters are installed side by side on a vertical DIN rail without any space in between. ● Several compact starters are installed side by side in a SIRIUS 3RA6 infeed system without any space in between.
Maximum rated current Depending on the current setting range, the following maximum rated currents apply to the compact starter: Table 4-1 Maximum rated current (3RA6 compact starter) SIRIUS 3RA6 Compact Starter 26 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 Internal control cabinet temperatures Permissible rated current Ir max + 40 °C 100% of Ir max + 60 °C 80% of Ir max Current setting range Max. rated current 0.1 to 0.4 A 0.4 A 0.32 to 1.25 A 1.25 A 1 to 4 A 4 A 3 to 12 A 12 A 8 to 32 A 32 A