Siemens — 5 Communication via AS-Interface

Communication via AS-Interface 5 The actuator sensor interface (AS-Interface) is a modular networking system for sensors and actuators at the lowest field level. As far as the program in the control system is concerned, it makes no difference whether parallel wiring is used or whether the AS-Interface is used. As a result, it is possible to switch over to the AS-Interface even on existing systems, as you can continue to use any programs that are already installed. The entire system can be operated without additional software. You do not need to know about the internal workings of the AS-Interface.

Replacement for wire bundle If parallel wiring is used for the compact starter, a large amount of wiring will be required for the purpose of transferring process signals to the control system. This means that each compact starter has to be connected to the control system by means of its own separate line. However, if the AS-Interface is used instead, this wire bundle can be replaced by a single two-wire line that is shared by all compact starter groups (up to a maximum of 62 compact starters). Data and power via one two-wire line The master communicates with the nodes via the AS-Interface lines.

As well as being used for data exchange, this line also carries the supply voltage for the electronics and the check-back signals of the compact starter. The voltage is fed into the AS-Interface line by a special AS-Interface power supply unit with data decoupling circuit. Auxiliary power The AS-i mounting module features a separate external 24 VDC auxiliary power supply, which is intended for the outputs. This meets the requirements of EN / DIN EN 50178 in respect of safe isolation of the auxiliary voltage from the AS-i potential. Consequently, compact starter control can be safely deactivated via Y1 - Y4.

Maximum system configuration For detailed installation and mounting guidelines, please refer to the manual entitled "AS-Interface System" (order number: 3RK2703-3AB02-1AA1). Up to 62 nodes (e.g. compact starters) can be connected to the AS-Interface line. This is possible thanks to the use of A/B technology, whereby the 31 addresses are split into two completely separate sub-addresses (e.g. 1A and 1B). SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 39