Installation/Removal 8.1 Installing the SIRIUS 3RA6 compact starter and AS-i mounting module 8.1.4 Installing the AS-i mounting module Requirements NOTICE There is a risk of damage to the AS-i mounting module. If you install the AS-i mounting module on a compact starter that has a control voltage of more than 24 V, the AS-i mounting module will be supplied with too much power. This will damage the AS-i mounting module. Only install the AS-i mounting module on a compact starter with a control voltage of 24 V. NOTICE There is a risk of damage to the AS-i mounting module. When installing the AS-i mounting module, please observe the ESD regulations, as electrostatic charging can damage it.
● The auxiliary and control conductor terminal blocks must be removed from the compact starter (24 V) (for information on removing the auxiliary and control conductor terminal blocks, please refer to "Installing/Removing auxiliary and control conductor terminal blocks (Page 135)"). ● The compact starter must be switched off (actuator set to OFF position). Procedure SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 63 Step Instructions Image 1 Insert the AS-i mounting module into the mechanically coded guiderail on the device from the bottom and then push it back until you hear it engage. 1