Siemens — 8.2.2 Removing the compact starter from a level surface (screw fastening)

Installation/Removal 8.2 Removing the SIRIUS 3RA6 compact starter and AS-i mounting module 8.2.2 Removing the compact starter from a level surface (screw fastening) Requirements ● The control and auxiliary conductor terminals must be disconnected. ● The compact starter must be switched off (actuator set to OFF position). DANGER Danger, high voltage! If removing the compact starter when the system is live, you must remember to set the actuator to the OFF position first, otherwise the compact starter could get damaged and you could get an electric shock. Procedure Note The compact starter can be removed from the wall with the wiring still in place (permanent wiring), i.e.

there is no need to disconnect the main conductor terminal blocks. SIRIUS 3RA6 Compact Starter System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 65 Step Instructions Image 1 Use a screwdriver to release the top main conductor terminal block. 1 1 2 4 4 3 2 Tilt the compact starter forwards so that there is no risk of it snapping back into the main conductor terminal block. 3 Use a screwdriver to release the bottom main conductor terminal block. 4 Tilt the compact starter upwards and pull it forwards in order to remove it from the main conductor terminal blocks.