Connecting 9.4 Connecting the compact starter (24 V) with optional AS-i mounting module 9.4.2 Connecting limit switches The AS-i mounting module for compact starters with two local inputs for safe shutdown (3RA6970-3B) can have equipment such as a limit switch connected to it. Consequently, safe shutdown up to category 2 in accordance with EN ISO 13849-1 is supported. When the contacts open, the limit switch function immediately shuts down the compact starter. The direct starter is shut down via Y1 - Y2. In the case of the reversing starter, shutdown is direction-specific and takes place via Y1 - Y2 for direction of rotation 1 and via Y3 - Y4 for direction of rotation 2.
Pin assignment of limit switch terminal Table 9-5 Limit switch terminal Conductor cross-sections of limit switch terminal Table 9-6 Conductor cross-sections of limit switch terminal Note If no limit switch is connected to the limit switch terminals, terminals Y1 - Y2 will need to be jumpered on the direct starter and terminals Y1 - Y2 and Y3 - Y4 will need to be jumpered on the reversing starter.
SIRIUS 3RA6 Compact Starter 78 System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02 Interface Meaning Image Y1, Y2 Connecting terminals for limit switch 1 for safe shutdown of "direction of rotation 1" Y3, Y4 Connecting terminals for limit switch 2 for safe shutdown of "direction of rotation 2" (only if mounting a reversing starter) Limit switch terminal (0.5 x 3.0) mm DIN ISO 2380-A 0,5 ... 0.6 Nm (4.5 to 5.3 lb·in) 1 x (0.5 … 2.5) mm2 2 x (0.5 … 1) mm2 1 x (0.5 … 2.5) mm2 2 x (0.5 … 1) mm2 AWG 1 x (20 to 12)